Added error code when array option is passed to special properties ALL, OPTIONAL, REQUIRED.

This commit is contained in:
skarg
2010-07-16 14:34:15 +00:00
parent 0b5efa5be5
commit 7852309f7e
+43 -25
View File
@@ -174,14 +174,14 @@ static int RPM_Encode_Property(
* - if decoding fails
* - if the response would be too large
* - the result from each included read request, if it succeeds
* - an Error if processing fails for all, or individual errors if only some fail,
* - an Error if processing fails for all, or individual errors if only some fail,
* or there isn't enough room in the APDU to fit the data.
*
*
* @param service_request [in] The contents of the service request.
* @param service_len [in] The length of the service_request.
* @param src [in] BACNET_ADDRESS of the source of the message
* @param service_data [in] The BACNET_CONFIRMED_SERVICE_DATA information
* decoded from the APDU header of this message.
* @param service_data [in] The BACNET_CONFIRMED_SERVICE_DATA information
* decoded from the APDU header of this message.
*/
void handler_read_property_multiple(
uint8_t * service_request,
@@ -227,7 +227,7 @@ void handler_read_property_multiple(
len =
rpm_decode_object_id(&service_request[decode_len],
service_len - decode_len, &rpmdata);
if (len >= 0) { /* Got one so skip to next stage */
if (len >= 0) { /* Got one so skip to next stage */
decode_len += len;
} else { /* bad encoding - skip to error/reject/abort handling */
#if PRINT_ENABLED
@@ -265,7 +265,6 @@ void handler_read_property_multiple(
error = len;
goto RPM_FAILURE;
}
decode_len += len;
/* handle the special properties */
if ((rpmdata.object_property == PROP_ALL) ||
@@ -276,27 +275,31 @@ void handler_read_property_multiple(
unsigned index = 0;
BACNET_PROPERTY_ID special_object_property;
special_object_property = rpmdata.object_property;
Device_Objects_Property_List(rpmdata.object_type, &property_list);
property_count =
RPM_Object_Property_Count(&property_list,
special_object_property);
if (property_count == 0) {
/* handle the error code - but use the special property */
if (rpmdata.array_index != BACNET_ARRAY_ALL) {
/* No array index options for this special property.
Encode error for this object property response */
len =
RPM_Encode_Property(&Handler_Transmit_Buffer[0],
(uint16_t)(npdu_len + apdu_len), MAX_APDU, &rpmdata);
if (len > 0) {
apdu_len += len;
} else {
error = len;
rpm_ack_encode_apdu_object_property_error(&Temp_Buf[0],
ERROR_CLASS_PROPERTY,
ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY);
copy_len =
memcopy(&Handler_Transmit_Buffer[0],
&Temp_Buf[0], npdu_len + apdu_len,
len, sizeof(Handler_Transmit_Buffer));
if (copy_len == 0) {
rpmdata.error_code = ERROR_CODE_ABORT_SEGMENTATION_NOT_SUPPORTED;
error = BACNET_STATUS_ABORT;
goto RPM_FAILURE;
}
apdu_len += len;
} else {
for (index = 0; index < property_count; index++) {
rpmdata.object_property =
RPM_Object_Property(&property_list,
special_object_property, index);
special_object_property = rpmdata.object_property;
Device_Objects_Property_List(rpmdata.object_type, &property_list);
property_count =
RPM_Object_Property_Count(&property_list,
special_object_property);
if (property_count == 0) {
/* handle the error code - but use the special property */
len =
RPM_Encode_Property(&Handler_Transmit_Buffer[0],
(uint16_t)(npdu_len + apdu_len), MAX_APDU, &rpmdata);
@@ -306,6 +309,21 @@ void handler_read_property_multiple(
error = len;
goto RPM_FAILURE;
}
} else {
for (index = 0; index < property_count; index++) {
rpmdata.object_property =
RPM_Object_Property(&property_list,
special_object_property, index);
len =
RPM_Encode_Property(&Handler_Transmit_Buffer[0],
(uint16_t)(npdu_len + apdu_len), MAX_APDU, &rpmdata);
if (len > 0) {
apdu_len += len;
} else {
error = len;
goto RPM_FAILURE;
}
}
}
}
} else {
@@ -358,7 +376,7 @@ void handler_read_property_multiple(
RPM_FAILURE:
if (error) {
if (error == BACNET_STATUS_ABORT) {
/* Kludge alert! At the moment we assume any abort is due to
/* Kludge alert! At the moment we assume any abort is due to
* to space issues due to segmentation or lack thereof. I wanted to show the proper
* handling via the abort_convert_error_code() so I put the error code
* in here, if you are sure all aborts properly set up the error_code then
@@ -375,7 +393,7 @@ void handler_read_property_multiple(
} else if (error == BACNET_STATUS_ERROR){
apdu_len =
bacerror_encode_apdu(&Handler_Transmit_Buffer[npdu_len],
service_data->invoke_id, SERVICE_CONFIRMED_READ_PROPERTY,
service_data->invoke_id, SERVICE_CONFIRMED_READ_PROP_MULTIPLE,
rpmdata.error_class, rpmdata.error_code);
#if PRINT_ENABLED
fprintf(stderr, "RP: Sending Error!\n");