- Introduced new enum value `kShortDiagnosticBit` to `GatewayModbusGeneratedKind`. - Enhanced `GatewayModbusPoint` and `GatewayModbusPointBinding` structures to include diagnostic snapshot, boolean key, and device type. - Added new diagnostic bit specifications and updated the corresponding arrays for generated discrete inputs and holding registers. - Implemented `addGeneratedDiagnosticPoint` function to handle the creation of diagnostic points. - Updated `rebuildMap` method to include generated diagnostic points during the map rebuilding process. Co-authored-by: Copilot <copilot@github.com>
156 lines
4.5 KiB
C++
156 lines
4.5 KiB
C++
#pragma once
|
|
|
|
#include "bridge.hpp"
|
|
#include "bridge_model.hpp"
|
|
#include "model_value.hpp"
|
|
|
|
#include <cstddef>
|
|
#include <cstdint>
|
|
#include <optional>
|
|
#include <string>
|
|
#include <vector>
|
|
|
|
namespace gateway {
|
|
|
|
constexpr uint16_t kGatewayModbusDefaultTcpPort = 1502;
|
|
constexpr size_t kGatewayModbusMaxPduBytes = 252;
|
|
constexpr uint16_t kGatewayModbusMaxReadBits = 2000;
|
|
constexpr uint16_t kGatewayModbusMaxReadRegisters = 125;
|
|
constexpr uint16_t kGatewayModbusMaxWriteBits = 1968;
|
|
constexpr uint16_t kGatewayModbusMaxWriteRegisters = 123;
|
|
|
|
struct GatewayModbusConfig {
|
|
std::string transport{"tcp-server"};
|
|
std::string host;
|
|
uint16_t port{kGatewayModbusDefaultTcpPort};
|
|
uint8_t unit_id{1};
|
|
};
|
|
|
|
enum class GatewayModbusSpace : uint8_t {
|
|
kCoil = 1,
|
|
kDiscreteInput = 2,
|
|
kHoldingRegister = 3,
|
|
kInputRegister = 4,
|
|
};
|
|
|
|
enum class GatewayModbusAccess : uint8_t {
|
|
kReadOnly = 0,
|
|
kWriteOnly = 1,
|
|
kReadWrite = 2,
|
|
};
|
|
|
|
enum class GatewayModbusGeneratedKind : uint8_t {
|
|
kNone = 0,
|
|
kShortOn,
|
|
kShortOff,
|
|
kShortRecallMax,
|
|
kShortRecallMin,
|
|
kShortDiscovered,
|
|
kShortOnline,
|
|
kShortSupportsDt1,
|
|
kShortSupportsDt4,
|
|
kShortSupportsDt5,
|
|
kShortSupportsDt6,
|
|
kShortSupportsDt8,
|
|
kShortGroupMaskKnown,
|
|
kShortActualLevelKnown,
|
|
kShortSceneKnown,
|
|
kShortSettingsKnown,
|
|
kShortControlGearPresent,
|
|
kShortLampFailure,
|
|
kShortLampPowerOn,
|
|
kShortLimitError,
|
|
kShortFadingCompleted,
|
|
kShortResetState,
|
|
kShortMissingShortAddress,
|
|
kShortPowerSupplyFault,
|
|
kShortBrightness,
|
|
kShortColorTemperature,
|
|
kShortGroupMask,
|
|
kShortPowerOnLevel,
|
|
kShortSystemFailureLevel,
|
|
kShortMinLevel,
|
|
kShortMaxLevel,
|
|
kShortFadeTime,
|
|
kShortFadeRate,
|
|
kShortInventoryState,
|
|
kShortPrimaryType,
|
|
kShortTypeMask,
|
|
kShortActualLevel,
|
|
kShortSceneId,
|
|
kShortRawStatus,
|
|
kShortDiagnosticBit,
|
|
};
|
|
|
|
struct GatewayModbusPoint {
|
|
GatewayModbusSpace space{GatewayModbusSpace::kHoldingRegister};
|
|
GatewayModbusAccess access{GatewayModbusAccess::kReadWrite};
|
|
uint16_t address{0};
|
|
std::string id;
|
|
std::string name;
|
|
bool generated{false};
|
|
GatewayModbusGeneratedKind generated_kind{GatewayModbusGeneratedKind::kNone};
|
|
int short_address{-1};
|
|
std::string model_id;
|
|
BridgeOperation operation{BridgeOperation::unknown};
|
|
std::optional<int> bit_index;
|
|
std::string diagnostic_snapshot;
|
|
std::string diagnostic_bool;
|
|
int diagnostic_device_type{-1};
|
|
};
|
|
|
|
struct GatewayModbusPointBinding {
|
|
std::string model_id;
|
|
GatewayModbusSpace space{GatewayModbusSpace::kHoldingRegister};
|
|
uint16_t address{0};
|
|
std::string id;
|
|
std::string name;
|
|
bool generated{false};
|
|
GatewayModbusGeneratedKind generated_kind{GatewayModbusGeneratedKind::kNone};
|
|
int short_address{-1};
|
|
GatewayModbusAccess access{GatewayModbusAccess::kReadWrite};
|
|
std::optional<int> bit_index;
|
|
std::string diagnostic_snapshot;
|
|
std::string diagnostic_bool;
|
|
int diagnostic_device_type{-1};
|
|
};
|
|
|
|
std::optional<GatewayModbusConfig> GatewayModbusConfigFromValue(const DaliValue* value);
|
|
DaliValue GatewayModbusConfigToValue(const GatewayModbusConfig& config);
|
|
|
|
const char* GatewayModbusSpaceToString(GatewayModbusSpace space);
|
|
const char* GatewayModbusAccessToString(GatewayModbusAccess access);
|
|
const char* GatewayModbusGeneratedKindToString(GatewayModbusGeneratedKind kind);
|
|
|
|
int GatewayModbusHumanAddressFromWire(GatewayModbusSpace space, uint16_t zero_based_address);
|
|
std::optional<GatewayModbusSpace> GatewayModbusReadSpaceForFunction(uint8_t function_code);
|
|
std::optional<GatewayModbusSpace> GatewayModbusWriteSpaceForFunction(uint8_t function_code);
|
|
|
|
class GatewayModbusBridge {
|
|
public:
|
|
explicit GatewayModbusBridge(DaliBridgeEngine& engine);
|
|
|
|
void setConfig(const GatewayModbusConfig& config);
|
|
const GatewayModbusConfig& config() const;
|
|
|
|
void rebuildMap();
|
|
std::optional<GatewayModbusPoint> findPoint(GatewayModbusSpace space,
|
|
uint16_t address) const;
|
|
std::vector<GatewayModbusPointBinding> describePoints() const;
|
|
std::vector<GatewayModbusPointBinding> describeHoldingRegisters() const;
|
|
|
|
DaliBridgeResult readModelPoint(const GatewayModbusPoint& point) const;
|
|
DaliBridgeResult writeRegisterPoint(const GatewayModbusPoint& point, uint16_t value) const;
|
|
DaliBridgeResult writeCoilPoint(const GatewayModbusPoint& point, bool value) const;
|
|
|
|
private:
|
|
DaliBridgeResult executeModelPoint(const GatewayModbusPoint& point,
|
|
std::optional<int> value) const;
|
|
|
|
DaliBridgeEngine& engine_;
|
|
GatewayModbusConfig config_;
|
|
std::vector<GatewayModbusPoint> points_;
|
|
};
|
|
|
|
} // namespace gateway
|