Add diagnostic bit support to Gateway Modbus
- Introduced new enum value `kShortDiagnosticBit` to `GatewayModbusGeneratedKind`. - Enhanced `GatewayModbusPoint` and `GatewayModbusPointBinding` structures to include diagnostic snapshot, boolean key, and device type. - Added new diagnostic bit specifications and updated the corresponding arrays for generated discrete inputs and holding registers. - Implemented `addGeneratedDiagnosticPoint` function to handle the creation of diagnostic points. - Updated `rebuildMap` method to include generated diagnostic points during the map rebuilding process. Co-authored-by: Copilot <copilot@github.com>
This commit is contained in:
@@ -13,7 +13,7 @@ This folder hosts the native ESP-IDF C++ rewrite of the Lua DALI gateway.
|
||||
- `gateway_cache/`: DALI scene/group/settings/runtime cache used by controller reconciliation and protocol bridges.
|
||||
- `gateway_bridge/`: per-channel bridge provisioning, command execution, protocol startup, and HTTP bridge actions.
|
||||
- `gateway_modbus/`: gateway-owned Modbus TCP config, generated DALI point tables, and provisioned Modbus model override dispatch.
|
||||
- `gateway_bacnet/`: BACnet/IP server adapter backed by bacnet-stack.
|
||||
- `gateway_bacnet/`: BACnet/IP server adapter backed by bacnet-stack, including the gateway-owned BACnet bridge model adapter.
|
||||
- `gateway_ble/`: NimBLE GATT bridge for BLE transport parity on `FFF1`/`FFF2`/`FFF3`, including raw DALI notifications.
|
||||
- `gateway_controller/`: Lua-compatible gateway command dispatcher, internal scene/group state, and notification fan-out.
|
||||
- `gateway_network/`: HTTP `/info`, `/dali/cmd`, `/led/1`, `/led/0`, `/jq.js`, UDP port `2020` command/notify routing, Wi-Fi STA lifecycle, ESP-Touch smartconfig, setup AP mode, ESP-NOW setup ingress, and BOOT-button Wi-Fi reset for the native gateway.
|
||||
@@ -35,4 +35,24 @@ The first generated map slice creates stable points for every DALI short address
|
||||
- Holding registers: writable brightness, color temperature, group mask, power-on level, system-failure level, min/max level, and fade time.
|
||||
- Input registers: read-only inventory state, primary type, type mask, cached actual level, scene id, raw status placeholder, group mask, and cached settings.
|
||||
|
||||
Unknown numeric values read as `0xFFFF`; booleans read as false unless inventory or cache state proves otherwise. Provisioned Modbus models still work as overrides at their configured Modbus point, and normal generated reads prefer gateway cache state to avoid DALI bus polling.
|
||||
Unknown numeric values read as `0xFFFF`; booleans read as false unless inventory or cache state proves otherwise. Provisioned Modbus models still work as overrides at their configured Modbus point, and normal generated reads prefer gateway cache state to avoid DALI bus polling.
|
||||
|
||||
An extension discrete-input range starts immediately after the legacy `0-63` short-address block. It publishes decoded DALI status, failure, and feature bits as individual booleans for base status, DT1 emergency, DT4/5/6 control-gear feature/failure status, and DT8 color status/features. This keeps existing Modbus addresses stable while making bit-level diagnostics readable without consumers masking packed status registers.
|
||||
|
||||
## BACnet/IP
|
||||
|
||||
BACnet/IP is owned by `gateway/components/gateway_bacnet` and is started through the per-channel bridge service. Runtime BACnet server settings live under top-level `bacnetServer` in bridge config:
|
||||
|
||||
```json
|
||||
{
|
||||
"bacnetServer": {
|
||||
"deviceInstance": 4194303,
|
||||
"localAddress": "",
|
||||
"udpPort": 47808
|
||||
}
|
||||
}
|
||||
```
|
||||
|
||||
Provisioned BACnet models still use generic `BridgeModel` fields such as object type, object instance, property, and optional `bitIndex`. Query-style models refresh BACnet `Present_Value` from live DALI reads, and binary models with `bitIndex` expose a single packed status bit.
|
||||
|
||||
For discovered DALI short addresses, the gateway also mirrors the generated Modbus discrete diagnostics as BACnet binary-input objects. Object instances are allocated in a gateway-owned generated range using the channel index plus the generated Modbus discrete-input offset, so generated objects stay deterministic while avoiding the provisioned-object address space in normal deployments.
|
||||
Reference in New Issue