Files
bacnet_stack/ports/win32
Steve Karg 1f591db6e7 Feature/mstp zero config option (#564)
* Added a MS/TP zero-config (automatically choose an unused MAC address) using an algorithm that starts with MAC=64 and waits for a random number of PFM (minimum of 8 plus modulo 64) before attempting to choose a MAC sequentially from 64..127. The confirmation uses a 128-bit UUID with the MSTP Test Request frame. The modifications are in src/bacnet/datalink/mstp.c and src/bacnet/datalink/dlmstp.c modules enabling any device to use zero-config if enabled. A working demonstration is in the ports/stm32f4xx for the NUCLEO board. Complete unit testing is included.  Options include lurking forever (wait for a router or another master node before joining) or lurking for a minimum time (enables self forming automatic MAC addressing device nodes).
2024-02-02 11:18:20 -06:00
..
2019-10-08 23:47:53 -05:00
2020-05-24 09:19:52 -05:00
2019-10-20 13:46:21 -05:00
2019-10-20 13:46:21 -05:00
2024-02-02 11:18:20 -06:00
2024-02-02 11:18:20 -06:00
2019-10-08 23:47:53 -05:00
2019-10-08 23:47:53 -05:00

Win32 ports for BACnet

This directory contains a demo program that compiles with a Win32 compiler. It was tested with the free MinGW32 MSYS2 GCC compiler and the (free) Microsoft Visual Studio Community Edition

Building with Makefile under MinGW32

Note: Building for 64-bit with MinGW64 requires extra runtimes, whereas building for 32-bit as Win32 doesn't require any other files for the EXE to work in any version of Windows.

  • MSYS2 installation is (from powershell):

    c:> winget install --id=MSYS2.MSYS2 -e

  • Start MSYS shell, and install MinGW32.

    $ pacman -Syu mingw-w64-i686-toolchain

  • Edit ~/.bashrc file and add:

    alias make=mingw32-make.exe

  • Exit MSYS.

  • Start MSYS profile for MinGW32.

  • Verify MSYS profile:

    $ uname

    MINGW32_NT-10.0-19045

  • Verify GCC is targeting i686:

    $ gcc -dumpmachine

    i686-w64-mingw32

  • Verify make is built for Windows32:

    make --version

    Built for Windows32

Building and running with Microsoft Visual Studio

  • Obtain the (free) Microsoft Visual Studio Community Edition, or use your professional version. Currently tested to MSVC 2022
  • Open solution file ports/win32/Microsoft Visual Studio/bacnet-stack.sln
  • Set startup project to be the desired application project, e.g. "server"
  • In the active project properties, debugging, set command line to desired DeviceID
  • In active project properties, debugging, set environment variables as appropriate, e.g. BACNET_IFACE=10.59.2.1 BACNET_IP_PORT=53004
  • Compile & run
  • Questions? edward@bac-test.com