skarg e53f38dd40 Changed the MSTP_MASTER_STATE_ANSWER_DATA_REQUEST state to always send a REPLY_POSTPONED by
commenting out the section that checks for new packets to send.  It was not the intent of the BACnet standard, but it makes the Master Node FSM compliant.  It's either that or re-parse the message for a matching apdu and invoke id, and then defer if the next message does not match.  The problem happens when an unconfirmed request (i.e. WhoIs) is followed immediated by a confirmed request (i.e. ReadProperty) before the device can respond to the unconfirmed request (i.e. the I-Am is queued in the Transmit buffer).
2007-07-14 00:09:16 +00:00
skarg 3869b55fea Updating Win32 MSTP datalink layer. Testing. 2007-07-03 00:44:48 +00:00
skarg d6851d7320 Updated the dlmstp and rx_fsm projects under Win32. Passing tokens and NPDU on MS/TP at 38400. 2007-07-02 23:09:22 +00:00
skarg 17eb5d9789 Testing MS/TP on Windows. 2007-06-29 23:11:57 +00:00
skarg 1824d4a95e Testing the MS/TP datalink layer on Linux. 2007-06-29 22:46:19 +00:00
skarg b3fda233cf Added MS/TP on Win32 port using external USB RS-485 device from SerialGear. Only completed RS-485 and dlmst unit testing. It is communicating but not nicely. 2007-06-26 22:32:43 +00:00