@@ -4,7 +4,8 @@ This tool captures MS/TP packets on an RS485 serial interface,
and saves the packets to a file in Wireshark PCAP format for
the MS/TP dissector to read. The filename has a date and time
code in it, and will contain up to 65535 packets. A new file
will be created at each 65535 packet interval.
will be created at each 65535 packet interval. The tool can
be stopped by using Control-C.
Here is a sample of the tool running (use CTRL-C to quit).
D:\code\bacnet-stack\bin>mstpcap COM3 38400
@@ -19,15 +20,35 @@ MAC MaxMstr Tokens Retries Treply Tusage Trpfm Tder Tpostpd
MS/TP capture tool also includes statistics which are listed for
any MAC addresses found passing a token,
or any MAC address replying to a DER message.
The statistics are emitted when CTRL-C is pressed, or when
The statistics are emitted when Control-C is pressed, or when
65535 packets are captured and the new file is created.
The statistics are cleared when the new file is created.
MaxMstr = highest destination MAC during PFM
Tokens = number of tokens transmitted
Retries = number of second tokens sent to this MAC
Treply = max milliseconds it took to reply with a token after receiving a token
Tusage = max Tusage_delay in milliseconds based on PFM and subsequent token
Trpfm = max milliseconds to respond to PFM with RPFM.
Tder = max milliseconds to respond to DER request with DNER
Tpostpd = max milliseconds to respond to DER request with Reply Postponed.
MaxMstr = highest destination MAC address during PFM
Tokens = number of tokens transmitted by this MAC address.
Retries = number of second tokens sent to this MAC address.
Treply = maximum number of milliseconds it took to reply with
a token after receiving a token. Treply is required to be less
than 25ms (but the mstpcap tool may not have that good of
resolution on Windows).
Tusage = the maximum number of milliseconds the
device waits for a ReplyToPollForMaster or Token retry.
Tusage is required to be between 20ms and 100ms.
Trpfm = maximum number of milliseconds to respond to PFM with RPFM. It is
required to be less than 25ms.
Tder = maximum number of milliseconds that a device takes to
respond to a DataExpectingReply request. Tder is required to be less
than 250ms.
Tpostpd = maximum number of milliseconds to respond to
DataExpectingReply request with ReplyPostponed. Tpostpd is
required to be less than 250ms.
Note that the mstpcap tool may not have that good of