Added test for shed type amount.

This commit is contained in:
Steve Karg
2025-12-15 16:16:51 -06:00
parent 37e45bbb6a
commit df335343f3
+63
View File
@@ -692,6 +692,7 @@ static void testLoadControlStateMachine(void)
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_INACTIVE, NULL);
test_teardown(object_instance);
/* SHED TYPE PERCENT - 20% */
test_setup(object_instance);
status = Load_Control_Valid_Instance(object_instance);
@@ -727,6 +728,68 @@ static void testLoadControlStateMachine(void)
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_COMPLIANT, NULL);
test_teardown(object_instance);
/* SHED TYPE AMOUNT - default value 0.0 watts */
test_setup(object_instance);
status = Load_Control_Valid_Instance(object_instance);
zassert_true(status, NULL);
status = Load_Control_Update_Interval_Set(object_instance, 0);
zassert_true(status, NULL);
Load_Control_WriteProperty_Enable(object_instance, true);
shed_level.type = BACNET_SHED_TYPE_AMOUNT;
shed_level.value.amount = 0.0f;
status =
Load_Control_Requested_Shed_Level_Set(object_instance, &shed_level);
zassert_true(status, NULL);
Load_Control_WriteProperty_Start_Time(
object_instance, 2007, 2, 27, 15, 0, 0, 0);
Load_Control_WriteProperty_Shed_Duration(object_instance, 5);
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 0, 0);
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
Load_Control_Timer(object_instance, 1);
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_REQUEST_PENDING, NULL);
Load_Control_Timer(object_instance, 1);
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_INACTIVE, NULL);
test_teardown(object_instance);
/* SHED TYPE PERCENT - 10.0 watts */
test_setup(object_instance);
status = Load_Control_Valid_Instance(object_instance);
zassert_true(status, NULL);
status = Load_Control_Update_Interval_Set(object_instance, 0);
zassert_true(status, NULL);
Load_Control_WriteProperty_Enable(object_instance, true);
shed_level.type = BACNET_SHED_TYPE_AMOUNT;
shed_level.value.amount = 10.0f;
status =
Load_Control_Requested_Shed_Level_Set(object_instance, &shed_level);
zassert_true(status, NULL);
Load_Control_WriteProperty_Start_Time(
object_instance, 2007, 2, 27, 15, 0, 0, 0);
Load_Control_WriteProperty_Shed_Duration(object_instance, 5);
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 0, 0);
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
Load_Control_Timer(object_instance, 1);
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_REQUEST_PENDING, NULL);
/* configure for non-compliance */
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 2, 0);
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
Load_Control_Timer(object_instance, 1);
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_NON_COMPLIANT, NULL);
/* configure for compliance - amount reference full-duty-baseline */
priority = Load_Control_Priority_For_Writing(object_instance);
status = Load_Control_Full_Duty_Baseline_Set(object_instance, 11.0f);
zassert_true(status, NULL);
Test_Present_Value_Priority_Set(10.0f, priority);
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 3, 0);
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
Load_Control_Timer(object_instance, 1);
shed_state = Load_Control_Present_Value(object_instance);
zassert_equal(shed_state, BACNET_SHED_COMPLIANT, NULL);
test_teardown(object_instance);
}