Corrected bug in all confirmed handlers: if a segmented message was received, the handler tried to decode it instead of immediately sending an abort. This caused lockup with WriteProperty.
This commit is contained in:
@@ -199,75 +199,79 @@ void handler_read_property(uint8_t * service_request,
|
||||
BACNET_ERROR_CODE error_code = ERROR_CODE_UNKNOWN_OBJECT;
|
||||
BACNET_ADDRESS my_address;
|
||||
|
||||
len = rp_decode_service_request(service_request, service_len, &data);
|
||||
/* encode the NPDU portion of the packet */
|
||||
datalink_get_my_address(&my_address);
|
||||
npdu_encode_npdu_data(&npdu_data, false, MESSAGE_PRIORITY_NORMAL);
|
||||
pdu_len = npdu_encode_pdu(&Handler_Transmit_Buffer[0], src,
|
||||
&my_address, &npdu_data);
|
||||
if (service_data->segmented_message) {
|
||||
/* we don't support segmentation - send an abort */
|
||||
len = abort_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id,
|
||||
ABORT_REASON_SEGMENTATION_NOT_SUPPORTED, true);
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr, "RP: Segmented message. Sending Abort!\n");
|
||||
#endif
|
||||
goto RP_ABORT;
|
||||
}
|
||||
|
||||
len = rp_decode_service_request(service_request, service_len, &data);
|
||||
#if PRINT_ENABLED
|
||||
if (len <= 0)
|
||||
fprintf(stderr, "Unable to decode Read-Property Request!\n");
|
||||
fprintf(stderr, "RP: Unable to decode Request!\n");
|
||||
#endif
|
||||
if (len < 0) {
|
||||
/* bad decoding - send an abort */
|
||||
len = abort_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id, ABORT_REASON_OTHER, true);
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr, "Sending Abort!\n");
|
||||
fprintf(stderr, "RP: Bad Encoding. Sending Abort!\n");
|
||||
#endif
|
||||
} else if (service_data->segmented_message) {
|
||||
/* we don't support segmentation - send an abort */
|
||||
len = abort_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id,
|
||||
ABORT_REASON_SEGMENTATION_NOT_SUPPORTED, true);
|
||||
goto RP_ABORT;
|
||||
}
|
||||
|
||||
/* assume that there is an error */
|
||||
error = true;
|
||||
len = Encode_Property_APDU(
|
||||
&Temp_Buf[0],
|
||||
data.object_type,
|
||||
data.object_instance,
|
||||
data.object_property,
|
||||
data.array_index,
|
||||
&error_class, &error_code);
|
||||
if (len >= 0) {
|
||||
/* encode the APDU portion of the packet */
|
||||
data.application_data = &Temp_Buf[0];
|
||||
data.application_data_len = len;
|
||||
/* FIXME: probably need a length limitation sent with encode */
|
||||
len =
|
||||
rp_ack_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id, &data);
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr, "Sending Abort!\n");
|
||||
fprintf(stderr,
|
||||
"RP: Sending Ack!\n");
|
||||
#endif
|
||||
} else {
|
||||
/* most cases will be error */
|
||||
error = true;
|
||||
len = Encode_Property_APDU(
|
||||
&Temp_Buf[0],
|
||||
data.object_type,
|
||||
data.object_instance,
|
||||
data.object_property,
|
||||
data.array_index,
|
||||
&error_class, &error_code);
|
||||
if (len >= 0) {
|
||||
/* encode the APDU portion of the packet */
|
||||
data.application_data = &Temp_Buf[0];
|
||||
data.application_data_len = len;
|
||||
/* FIXME: probably need a length limitation sent with encode */
|
||||
len =
|
||||
rp_ack_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id, &data);
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr,
|
||||
"Sending Read Property Ack!\n");
|
||||
#endif
|
||||
error = false;
|
||||
}
|
||||
error = false;
|
||||
}
|
||||
if (error) {
|
||||
switch (len) {
|
||||
if (len == -2) {
|
||||
/* BACnet APDU too small to fit data, so proper response is Abort */
|
||||
case -2:
|
||||
len = abort_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id,
|
||||
ABORT_REASON_SEGMENTATION_NOT_SUPPORTED, true);
|
||||
break;
|
||||
case -1:
|
||||
default:
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr, "RP: Reply too big to fit into APDU!\n");
|
||||
#endif
|
||||
} else {
|
||||
len = bacerror_encode_apdu(&Handler_Transmit_Buffer[pdu_len],
|
||||
service_data->invoke_id,
|
||||
SERVICE_CONFIRMED_READ_PROPERTY, error_class, error_code);
|
||||
break;
|
||||
}
|
||||
#if PRINT_ENABLED
|
||||
fprintf(stderr, "Sending Read Property Error!\n");
|
||||
fprintf(stderr, "RP: Sending Error!\n");
|
||||
#endif
|
||||
}
|
||||
}
|
||||
RP_ABORT:
|
||||
pdu_len += len;
|
||||
bytes_sent = datalink_send_pdu(src, &npdu_data,
|
||||
&Handler_Transmit_Buffer[0], pdu_len);
|
||||
|
||||
Reference in New Issue