Corrected RPM client handling - missed the AccessError tag. Thanks, Kevin!
This commit is contained in:
@@ -51,6 +51,8 @@ static int rpm_ack_decode_service_request(
|
||||
{
|
||||
int decoded_len = 0; /* return value */
|
||||
int len = 0; /* number of bytes returned from decoding */
|
||||
uint8_t tag_number = 0; /* decoded tag number */
|
||||
uint32_t len_value = 0; /* decoded length value */
|
||||
BACNET_READ_ACCESS_DATA *rpm_object;
|
||||
BACNET_READ_ACCESS_DATA *old_rpm_object;
|
||||
BACNET_PROPERTY_REFERENCE *rpm_property;
|
||||
@@ -89,6 +91,7 @@ static int rpm_ack_decode_service_request(
|
||||
apdu_len -= len;
|
||||
apdu += len;
|
||||
if (apdu_len && decode_is_opening_tag_number(apdu, 4)) {
|
||||
/* propertyValue */
|
||||
decoded_len++;
|
||||
apdu_len--;
|
||||
apdu++;
|
||||
@@ -115,6 +118,41 @@ static int rpm_ack_decode_service_request(
|
||||
old_value->next = value;
|
||||
}
|
||||
}
|
||||
} else if (apdu_len && decode_is_opening_tag_number(apdu, 5)) {
|
||||
/* propertyAccessError */
|
||||
decoded_len++;
|
||||
apdu_len--;
|
||||
apdu++;
|
||||
/* decode the class and code sequence */
|
||||
len =
|
||||
decode_tag_number_and_value(apdu, &tag_number,
|
||||
&len_value);
|
||||
decoded_len += len;
|
||||
apdu_len -= len;
|
||||
apdu += len;
|
||||
/* FIXME: we could validate that the tag is enumerated... */
|
||||
len = decode_enumerated(apdu, len_value,
|
||||
(int *)&rpm_property->error.error_class);
|
||||
decoded_len += len;
|
||||
apdu_len -= len;
|
||||
apdu += len;
|
||||
len =
|
||||
decode_tag_number_and_value(apdu, &tag_number,
|
||||
&len_value);
|
||||
decoded_len += len;
|
||||
apdu_len -= len;
|
||||
apdu += len;
|
||||
/* FIXME: we could validate that the tag is enumerated... */
|
||||
len = decode_enumerated(apdu, len_value,
|
||||
(int *)&rpm_property->error.error_code);
|
||||
decoded_len += len;
|
||||
apdu_len -= len;
|
||||
apdu += len;
|
||||
if (apdu_len && decode_is_closing_tag_number(apdu, 5)) {
|
||||
decoded_len++;
|
||||
apdu_len--;
|
||||
apdu++;
|
||||
}
|
||||
}
|
||||
old_rpm_property = rpm_property;
|
||||
rpm_property = calloc(1, sizeof(BACNET_PROPERTY_REFERENCE));
|
||||
@@ -163,6 +201,7 @@ static void PrintReadPropertyMultipleData(
|
||||
#endif
|
||||
}
|
||||
value = listOfProperties->value;
|
||||
if (value) {
|
||||
#if PRINT_ENABLED
|
||||
if (value->next) {
|
||||
fprintf(stdout, "{");
|
||||
@@ -187,6 +226,16 @@ static void PrintReadPropertyMultipleData(
|
||||
#endif
|
||||
value = value->next;
|
||||
}
|
||||
} else {
|
||||
#if PRINT_ENABLED
|
||||
/* AccessError */
|
||||
fprintf(stdout, "BACnet Error: %s: %s\r\n",
|
||||
bactext_error_class_name(
|
||||
(int)listOfProperties->error.error_class),
|
||||
bactext_error_code_name(
|
||||
(int)listOfProperties->error.error_code));
|
||||
#endif
|
||||
}
|
||||
listOfProperties = listOfProperties->next;
|
||||
}
|
||||
#if PRINT_ENABLED
|
||||
|
||||
@@ -89,11 +89,20 @@ typedef struct BACnet_Application_Data_Value {
|
||||
struct BACnet_Application_Data_Value *next;
|
||||
} BACNET_APPLICATION_DATA_VALUE;
|
||||
|
||||
struct BACnet_Access_Error;
|
||||
typedef struct BACnet_Access_Error {
|
||||
BACNET_ERROR_CLASS error_class;
|
||||
BACNET_ERROR_CODE error_code;
|
||||
} BACNET_ACCESS_ERROR;
|
||||
|
||||
struct BACnet_Property_Reference;
|
||||
typedef struct BACnet_Property_Reference {
|
||||
BACNET_PROPERTY_ID propertyIdentifier;
|
||||
int32_t propertyArrayIndex; /* optional */
|
||||
/* either value or error, but not both.
|
||||
Use NULL value to indicate error */
|
||||
BACNET_APPLICATION_DATA_VALUE *value;
|
||||
BACNET_ACCESS_ERROR error;
|
||||
/* simple linked list */
|
||||
struct BACnet_Property_Reference *next;
|
||||
} BACNET_PROPERTY_REFERENCE;
|
||||
|
||||