Corrected the COV lifetime to be seconds, not milliseconds.
This commit is contained in:
@@ -224,10 +224,10 @@ COV_FAILED:
|
||||
/* note: worst case tasking: MS/TP with the ability to send only
|
||||
one notification per task cycle */
|
||||
void handler_cov_task(
|
||||
uint32_t elapsed_milliseconds)
|
||||
uint32_t elapsed_seconds)
|
||||
{
|
||||
int index;
|
||||
int lifetime_milliseconds;
|
||||
int lifetime_seconds;
|
||||
BACNET_OBJECT_ID object_id;
|
||||
bool status = false;
|
||||
|
||||
@@ -236,9 +236,9 @@ void handler_cov_task(
|
||||
for (index = 0; index < MAX_COV_SUBCRIPTIONS; index++) {
|
||||
if (COV_Subscriptions[index].valid) {
|
||||
/* handle timeouts */
|
||||
lifetime_milliseconds = COV_Subscriptions[index].lifetime;
|
||||
if (lifetime_milliseconds >= elapsed_milliseconds) {
|
||||
COV_Subscriptions[index].lifetime -= elapsed_milliseconds;
|
||||
lifetime_seconds = COV_Subscriptions[index].lifetime;
|
||||
if (lifetime_seconds >= elapsed_seconds) {
|
||||
COV_Subscriptions[index].lifetime -= elapsed_seconds;
|
||||
} else {
|
||||
COV_Subscriptions[index].lifetime = 0;
|
||||
}
|
||||
|
||||
Reference in New Issue