Fixed the ReinitializeDevice and DeviceCommunicationControl password length checking for non-UTF8 passwords. (#914)
This commit is contained in:
@@ -668,6 +668,7 @@ bool Device_Reinitialize(BACNET_REINITIALIZE_DEVICE_DATA *rd_data)
|
||||
bool status = false;
|
||||
bool password_success = false;
|
||||
unsigned i;
|
||||
size_t length;
|
||||
|
||||
/* From 16.4.1.1.2 Password
|
||||
This optional parameter shall be a CharacterString of up to
|
||||
@@ -676,7 +677,12 @@ bool Device_Reinitialize(BACNET_REINITIALIZE_DEVICE_DATA *rd_data)
|
||||
is absent or if the password is incorrect. For those devices that
|
||||
do not require a password, this parameter shall be ignored.*/
|
||||
if (Reinit_Password && strlen(Reinit_Password) > 0) {
|
||||
if (characterstring_utf8_length(&rd_data->password) > 20) {
|
||||
if (characterstring_encoding(&rd_data->password) == CHARACTER_UTF8) {
|
||||
length = characterstring_utf8_length(&rd_data->password);
|
||||
} else {
|
||||
length = characterstring_length(&rd_data->password);
|
||||
}
|
||||
if (length > 20) {
|
||||
rd_data->error_class = ERROR_CLASS_SERVICES;
|
||||
rd_data->error_code = ERROR_CODE_PARAMETER_OUT_OF_RANGE;
|
||||
} else if (characterstring_ansi_same(
|
||||
|
||||
Reference in New Issue