Bugfix/print property name units lighting (#313)
* Fix EPICS property name proprietary range * Fix Lighting Command decode length * add function to determine property name and units proprietary range * improve test coverage for AI, AO, AV, BI, BO, BV, LO * refactor common property encoding to proplist module * add decoder for priority array Co-authored-by: Steve Karg <skarg@users.sourceforge.net>
This commit is contained in:
+29
-7
@@ -748,12 +748,24 @@ INDTEXT_DATA bacnet_property_names[] = {
|
||||
{ 0, NULL }
|
||||
};
|
||||
|
||||
bool bactext_property_name_proprietary(unsigned index)
|
||||
{
|
||||
bool status = false;
|
||||
|
||||
if ((index >= PROP_PROPRIETARY_RANGE_MIN) &&
|
||||
(index <= PROP_PROPRIETARY_RANGE_MAX)) {
|
||||
status = true;
|
||||
}
|
||||
|
||||
return status;
|
||||
}
|
||||
|
||||
const char *bactext_property_name(unsigned index)
|
||||
{
|
||||
/* Enumerated values 0-511 are reserved for definition by ASHRAE.
|
||||
Enumerated values 512-4194303 may be used by others subject to the
|
||||
procedures and constraints described in Clause 23. */
|
||||
if ((index >= 512) && (index <= 4194303)) {
|
||||
if (bactext_property_name_proprietary(index)) {
|
||||
return Vendor_Proprietary_String;
|
||||
} else {
|
||||
return indtext_by_index_default(
|
||||
@@ -1018,18 +1030,28 @@ INDTEXT_DATA bacnet_engineering_unit_names[] = {
|
||||
the procedures and constraints described in Clause 23. */
|
||||
};
|
||||
|
||||
bool bactext_engineering_unit_name_proprietary(unsigned index)
|
||||
{
|
||||
bool status = false;
|
||||
|
||||
if ((index >= UNITS_PROPRIETARY_RANGE_MIN) &&
|
||||
(index <= UNITS_PROPRIETARY_RANGE_MAX)) {
|
||||
status = true;
|
||||
} else if ((index >= UNITS_PROPRIETARY_RANGE_MIN2) &&
|
||||
(index <= UNITS_PROPRIETARY_RANGE_MAX2)) {
|
||||
status = true;
|
||||
}
|
||||
|
||||
return status;
|
||||
}
|
||||
|
||||
const char *bactext_engineering_unit_name(unsigned index)
|
||||
{
|
||||
if (index <= UNITS_RESERVED_RANGE_MAX) {
|
||||
return indtext_by_index_default(
|
||||
bacnet_engineering_unit_names, index, ASHRAE_Reserved_String);
|
||||
} else if (index <= UNITS_PROPRIETARY_RANGE_MAX) {
|
||||
if (bactext_engineering_unit_name_proprietary(index)) {
|
||||
return Vendor_Proprietary_String;
|
||||
} else if (index <= UNITS_RESERVED_RANGE_MAX2) {
|
||||
return indtext_by_index_default(
|
||||
bacnet_engineering_unit_names, index, ASHRAE_Reserved_String);
|
||||
} else if (index <= UNITS_PROPRIETARY_RANGE_MAX2) {
|
||||
return Vendor_Proprietary_String;
|
||||
}
|
||||
|
||||
return ASHRAE_Reserved_String;
|
||||
|
||||
Reference in New Issue