Updated the objects, services, and properties for the 135-2012 version of the BACnet standard.
This commit is contained in:
@@ -250,10 +250,7 @@ typedef enum {
|
||||
PROP_SHED_LEVEL_DESCRIPTIONS = 220,
|
||||
PROP_SHED_LEVELS = 221,
|
||||
PROP_STATE_DESCRIPTION = 222,
|
||||
/* enumerations 223-225 are used in Addendum i to ANSI/ASHRAE 135-2004 */
|
||||
PROP_FADE_TIME = 223,
|
||||
PROP_LIGHTING_COMMAND = 224,
|
||||
PROP_LIGHTING_COMMAND_PRIORITY = 225,
|
||||
/* enumerations 223-225 are unassigned */
|
||||
/* enumerations 226-235 are used in Addendum f to ANSI/ASHRAE 135-2004 */
|
||||
PROP_DOOR_ALARM_STATE = 226,
|
||||
PROP_DOOR_EXTENDED_PULSE_TIME = 227,
|
||||
@@ -265,15 +262,7 @@ typedef enum {
|
||||
PROP_LOCK_STATUS = 233,
|
||||
PROP_MASKED_ALARM_VALUES = 234,
|
||||
PROP_SECURED_STATUS = 235,
|
||||
/* enumerations 236-243 are used in Addendum i to ANSI/ASHRAE 135-2004 */
|
||||
PROP_OFF_DELAY = 236,
|
||||
PROP_ON_DELAY = 237,
|
||||
PROP_POWER = 238,
|
||||
PROP_POWER_ON_VALUE = 239,
|
||||
PROP_PROGRESS_VALUE = 240,
|
||||
PROP_RAMP_RATE = 241,
|
||||
PROP_STEP_INCREMENT = 242,
|
||||
PROP_SYSTEM_FAILURE_VALUE = 243,
|
||||
/* enumerations 236-243 are unassigned */
|
||||
/* enumerations 244-311 are used in Addendum j to ANSI/ASHRAE 135-2004 */
|
||||
PROP_ABSENTEE_LIMIT = 244,
|
||||
PROP_ACCESS_ALARM_EVENTS = 245,
|
||||
@@ -379,19 +368,53 @@ typedef enum {
|
||||
PROP_COVU_PERIOD = 349,
|
||||
PROP_COVU_RECIPIENTS = 350,
|
||||
PROP_EVENT_MESSAGE_TEXTS = 351,
|
||||
/* enumerations 352-363 are defined in Addendum 2010-af */
|
||||
PROP_EVENT_MESSAGE_TEXTS_CONFIG = 352,
|
||||
PROP_EVENT_DETECTION_ENABLE = 353,
|
||||
PROP_EVENT_ALGORITHM_INHIBIT = 354,
|
||||
PROP_EVENT_ALGORITHM_INHIBIT_REF = 355,
|
||||
PROP_TIME_DELAY_NORMAL = 356,
|
||||
PROP_RELIABILITY_EVALUATION_INHIBIT = 357,
|
||||
PROP_FAULT_PARAMETERS = 358,
|
||||
PROP_FAULT_TYPE = 359,
|
||||
PROP_LOCAL_FORWARDING_ONLY = 360,
|
||||
PROP_PROCESS_IDENTIFIER_FILTER = 361,
|
||||
PROP_SUBSCRIBED_RECIPIENTS = 362,
|
||||
PROP_PORT_FILTER = 363,
|
||||
/* enumeration 364 is defined in Addendum 2010-ae */
|
||||
PROP_AUTHORIZATION_EXEMPTIONS = 364,
|
||||
/* enumerations 365-370 are defined in Addendum 2010-aa */
|
||||
PROP_ALLOW_GROUP_DELAY_INHIBIT = 365,
|
||||
PROP_CHANNEL_NUMBER = 366,
|
||||
PROP_CONTROL_GROUPS = 367,
|
||||
PROP_EXECUTION_DELAY = 368,
|
||||
PROP_LAST_PRIORITY = 369,
|
||||
PROP_WRITE_STATUS = 370,
|
||||
/* enumeration 371 is defined in Addendum 2010-ao */
|
||||
PROP_PROPERTY_LIST = 371,
|
||||
/* enumeration 372 is defined in Addendum 2010-ak */
|
||||
PROP_SERIAL_NUMBER = 372,
|
||||
/* enumerations 373-386 are defined in Addendum 2010-i */
|
||||
PROP_BLINK_WARN_ENABLE = 373,
|
||||
PROP_DEFAULT_FADE_TIME = 374,
|
||||
PROP_DEFAULT_RAMP_RATE = 375,
|
||||
PROP_DEFAULT_STEP_INCREMENT = 376,
|
||||
PROP_EGRESS_TIMER = 377,
|
||||
PROP_IN_PROGRESS = 378,
|
||||
PROP_INSTANTANEOUS_POWER = 379,
|
||||
PROP_LIGHTING_COMMAND = 380,
|
||||
PROP_LIGHTING_COMMAND_DEFAULT_PRIORITY = 381,
|
||||
PROP_MAX_ACTUAL_VALUE = 382,
|
||||
PROP_MIN_ACTUAL_VALUE = 383,
|
||||
PROP_POWER = 384,
|
||||
PROP_TRANSITION = 385,
|
||||
PROP_EGRESS_ACTIVE = 386
|
||||
/* The special property identifiers all, optional, and required */
|
||||
/* are reserved for use in the ReadPropertyConditional and */
|
||||
/* ReadPropertyMultiple services or services not defined in this standard. */
|
||||
/* Enumerated values 0-511 are reserved for definition by ASHRAE. */
|
||||
/* Enumerated values 512-4194303 may be used by others subject to the */
|
||||
/* procedures and constraints described in Clause 23. */
|
||||
/* enumerations used to test Addendum i to ANSI/ASHRAE 135-2008 - private */
|
||||
PROP_BLINK_PRIORITY_THRESHOLD = 4201,
|
||||
PROP_BLINK_TIME = 4202,
|
||||
PROP_BINARY_ACTIVE_VALUE = 4203,
|
||||
PROP_BINARY_INACTIVE_VALUE = 4204
|
||||
} BACNET_PROPERTY_ID;
|
||||
|
||||
/* do the MAX as define rather than enumeration for devices
|
||||
@@ -916,7 +939,7 @@ typedef enum {
|
||||
OBJECT_LOAD_CONTROL = 28,
|
||||
OBJECT_STRUCTURED_VIEW = 29,
|
||||
OBJECT_ACCESS_DOOR = 30,
|
||||
OBJECT_LIGHTING_OUTPUT = 31,
|
||||
/* 31 was lighting output, but BACnet editor changed it... */
|
||||
OBJECT_ACCESS_CREDENTIAL = 32, /* Addendum 2008-j */
|
||||
OBJECT_ACCESS_POINT = 33,
|
||||
OBJECT_ACCESS_RIGHTS = 34,
|
||||
@@ -925,17 +948,21 @@ typedef enum {
|
||||
OBJECT_CREDENTIAL_DATA_INPUT = 37, /* authentication-factor-input */
|
||||
OBJECT_NETWORK_SECURITY = 38, /* Addendum 2008-g */
|
||||
OBJECT_BITSTRING_VALUE = 39, /* Addendum 2008-w */
|
||||
OBJECT_CHARACTERSTRING_VALUE = 40,
|
||||
OBJECT_DATE_PATTERN_VALUE = 41,
|
||||
OBJECT_DATE_VALUE = 42,
|
||||
OBJECT_DATETIME_PATTERN_VALUE = 43,
|
||||
OBJECT_DATETIME_VALUE = 44,
|
||||
OBJECT_INTEGER_VALUE = 45,
|
||||
OBJECT_LARGE_ANALOG_VALUE = 46,
|
||||
OBJECT_OCTETSTRING_VALUE = 47,
|
||||
OBJECT_POSITIVE_INTEGER_VALUE = 48,
|
||||
OBJECT_TIME_PATTERN_VALUE = 49,
|
||||
OBJECT_TIME_VALUE = 50,
|
||||
OBJECT_CHARACTERSTRING_VALUE = 40, /* Addendum 2008-w */
|
||||
OBJECT_DATE_PATTERN_VALUE = 41, /* Addendum 2008-w */
|
||||
OBJECT_DATE_VALUE = 42, /* Addendum 2008-w */
|
||||
OBJECT_DATETIME_PATTERN_VALUE = 43, /* Addendum 2008-w */
|
||||
OBJECT_DATETIME_VALUE = 44, /* Addendum 2008-w */
|
||||
OBJECT_INTEGER_VALUE = 45, /* Addendum 2008-w */
|
||||
OBJECT_LARGE_ANALOG_VALUE = 46, /* Addendum 2008-w */
|
||||
OBJECT_OCTETSTRING_VALUE = 47, /* Addendum 2008-w */
|
||||
OBJECT_POSITIVE_INTEGER_VALUE = 48, /* Addendum 2008-w */
|
||||
OBJECT_TIME_PATTERN_VALUE = 49, /* Addendum 2008-w */
|
||||
OBJECT_TIME_VALUE = 50, /* Addendum 2008-w */
|
||||
OBJECT_NOTIFICATION_FORWARDER = 51, /* Addendum 2010-af */
|
||||
OBJECT_ALERT_ENROLLMENT = 52, /* Addendum 2010-af */
|
||||
OBJECT_CHANNEL = 53, /* Addendum 2010-aa */
|
||||
OBJECT_LIGHTING_OUTPUT = 54, /* Addendum 2010-i */
|
||||
/* used for bit string loop */
|
||||
PROPRIETARY_BACNET_OBJECT_TYPE = 128,
|
||||
MAX_BACNET_OBJECT_TYPE = 1024
|
||||
@@ -1065,12 +1092,14 @@ typedef enum {
|
||||
SERVICE_UNCONFIRMED_WHO_HAS = 7,
|
||||
SERVICE_UNCONFIRMED_WHO_IS = 8,
|
||||
SERVICE_UNCONFIRMED_UTC_TIME_SYNCHRONIZATION = 9,
|
||||
/* addendum 2010-aa */
|
||||
SERVICE_UNCONFIRMED_WRITE_GROUP = 10,
|
||||
/* Other services to be added as they are defined. */
|
||||
/* All choice values in this production are reserved */
|
||||
/* for definition by ASHRAE. */
|
||||
/* Proprietary extensions are made by using the */
|
||||
/* UnconfirmedPrivateTransfer service. See Clause 23. */
|
||||
MAX_BACNET_UNCONFIRMED_SERVICE = 10
|
||||
MAX_BACNET_UNCONFIRMED_SERVICE = 11
|
||||
} BACNET_UNCONFIRMED_SERVICE;
|
||||
|
||||
/* Bit String Enumerations */
|
||||
@@ -1099,6 +1128,7 @@ typedef enum {
|
||||
SERVICE_SUPPORTED_READ_RANGE = 35,
|
||||
SERVICE_SUPPORTED_WRITE_PROPERTY = 15,
|
||||
SERVICE_SUPPORTED_WRITE_PROP_MULTIPLE = 16,
|
||||
SERVICE_SUPPORTED_WRITE_GROUP = 40,
|
||||
/* Remote Device Management Services */
|
||||
SERVICE_SUPPORTED_DEVICE_COMMUNICATION_CONTROL = 17,
|
||||
SERVICE_SUPPORTED_PRIVATE_TRANSFER = 18,
|
||||
@@ -1121,9 +1151,9 @@ typedef enum {
|
||||
SERVICE_SUPPORTED_UTC_TIME_SYNCHRONIZATION = 36,
|
||||
SERVICE_SUPPORTED_WHO_HAS = 33,
|
||||
SERVICE_SUPPORTED_WHO_IS = 34
|
||||
/* Other services to be added as they are defined. */
|
||||
/* All values in this production are reserved */
|
||||
/* for definition by ASHRAE. */
|
||||
/* Other services to be added as they are defined. */
|
||||
/* All values in this production are reserved */
|
||||
/* for definition by ASHRAE. */
|
||||
} BACNET_SERVICES_SUPPORTED;
|
||||
|
||||
typedef enum {
|
||||
|
||||