Creating a demo of the proposed Lighting Output object.
This commit is contained in:
+38
-8
@@ -258,24 +258,34 @@ typedef enum {
|
||||
PROP_DUTY_WINDOW = 213,
|
||||
PROP_EXPECTED_SHED_LEVEL = 214,
|
||||
PROP_FULL_DUTY_BASELINE = 215,
|
||||
/* note: missing enumerations for now */
|
||||
/* enumerations 216-217 are used in Addendum i to ANSI/ASHRAE 135-2004 */
|
||||
PROP_BLINK_PRIORITY_THRESHOLD = 216,
|
||||
PROP_BLINK_TIME = 217,
|
||||
PROP_REQUESTED_SHED_LEVEL = 218,
|
||||
PROP_SHED_DURATION = 219,
|
||||
PROP_SHED_LEVEL_DESCRIPTIONS = 220,
|
||||
PROP_SHED_LEVELS = 221,
|
||||
PROP_STATE_DESCRIPTION = 222,
|
||||
/* note: missing enumerations for now */
|
||||
/* enumerations 226-235 are used in Addendum f to
|
||||
ANSI/ASHRAE 135-2004 */
|
||||
PROP_LOG_DEVICE_OBJECT_PROPERTIES = 236,
|
||||
PROP_LOG_MULTIPLE_BUFFER = 237,
|
||||
/* enumerations 223-225 are used in Addendum i to ANSI/ASHRAE 135-2004 */
|
||||
PROP_FADE_TIME = 223,
|
||||
PROP_LIGHTING_COMMAND = 224,
|
||||
PROP_LIGHTING_COMMAND_PRIORITY = 225,
|
||||
/* enumerations 226-235 are used in Addendum f to ANSI/ASHRAE 135-2004 */
|
||||
/* enumerations 236-243 are used in Addendum i to ANSI/ASHRAE 135-2004 */
|
||||
PROP_OFF_DELAY = 236,
|
||||
PROP_ON_DELAY = 237,
|
||||
PROP_POWER = 238,
|
||||
PROP_POWER_ON_VALUE = 239,
|
||||
PROP_PROGRESS_VALUE = 240,
|
||||
PROP_RAMP_RATE = 241,
|
||||
PROP_STEP_INCREMENT = 242,
|
||||
PROP_SYSTEM_FAILURE_VALUE = 243,
|
||||
/* The special property identifiers all, optional, and required */
|
||||
/* are reserved for use in the ReadPropertyConditional and */
|
||||
/* ReadPropertyMultiple services or services not defined in this standard. */
|
||||
/* Enumerated values 0-511 are reserved for definition by ASHRAE. */
|
||||
/* Enumerated values 512-4194303 may be used by others subject to the */
|
||||
/* procedures and constraints described in Clause 23. */
|
||||
/* The highest enumeration used in this version is 168. */
|
||||
MAX_BACNET_PROPERTY_ID = 4194303
|
||||
} BACNET_PROPERTY_ID;
|
||||
|
||||
@@ -742,10 +752,12 @@ typedef enum {
|
||||
OBJECT_TREND_LOG_MULTIPLE = 27,
|
||||
OBJECT_LOAD_CONTROL = 28,
|
||||
OBJECT_STRUCTURED_VIEW = 29,
|
||||
/* what is object type 30? */
|
||||
OBJECT_LIGHTING_OUTPUT = 31,
|
||||
/* Enumerated values 0-127 are reserved for definition by ASHRAE. */
|
||||
/* Enumerated values 128-1023 may be used by others subject to */
|
||||
/* the procedures and constraints described in Clause 23. */
|
||||
MAX_ASHRAE_OBJECT_TYPE = 30, /* used for bit string loop */
|
||||
MAX_ASHRAE_OBJECT_TYPE = 32, /* used for bit string loop */
|
||||
MAX_BACNET_OBJECT_TYPE = 1023
|
||||
} BACNET_OBJECT_TYPE;
|
||||
|
||||
@@ -1206,4 +1218,22 @@ typedef enum BACnetShedState {
|
||||
BACNET_SHED_NON_COMPLIANT = 3
|
||||
} BACNET_SHED_STATE;
|
||||
|
||||
typedef enum BACnetLightingOperation {
|
||||
BACNET_LIGHTS_STOP = 0,
|
||||
BACNET_LIGHTS_FADE_TO = 1,
|
||||
BACNET_LIGHTS_FADE_TO_OVER = 2,
|
||||
BACNET_LIGHTS_RAMP_TO = 3,
|
||||
BACNET_LIGHTS_RAMP_TO_AT_RATE = 4,
|
||||
BACNET_LIGHTS_RAMP_UP = 5,
|
||||
BACNET_LIGHTS_RAMP_UP_AT_RATE = 6,
|
||||
BACNET_LIGHTS_RAMP_DOWN = 7,
|
||||
BACNET_LIGHTS_RAMP_DOWN_AT_RATE = 8,
|
||||
BACNET_LIGHTS_STEP_UP = 9,
|
||||
BACNET_LIGHTS_STEP_DOWN = 10,
|
||||
BACNET_LIGHTS_STEP_UP_BY = 11,
|
||||
BACNET_LIGHTS_STEP_DOWN_BY = 12,
|
||||
BACNET_LIGHTS_GOTO_LEVEL = 13,
|
||||
BACNET_LIGHTS_RELINQUISH = 14
|
||||
} BACNET_LIGHTING_OPERATION;
|
||||
|
||||
#endif /* end of BACENUM_H */
|
||||
|
||||
Reference in New Issue