2nd pass at changing the error/reject/abort status reporting to improve BTL test compliance. ReadProperty fully done for core and demo objects. Will tackle other services next.
This commit is contained in:
@@ -316,7 +316,7 @@ bool Multistate_Input_State_Text_Set(
|
||||
}
|
||||
|
||||
|
||||
/* return apdu len, or -1 on error */
|
||||
/* return apdu len, or BACNET_STATUS_ERROR on error */
|
||||
int Multistate_Input_Read_Property(
|
||||
BACNET_READ_PROPERTY_DATA * rpdata)
|
||||
{
|
||||
@@ -416,7 +416,7 @@ int Multistate_Input_Read_Property(
|
||||
} else {
|
||||
rpdata->error_class = ERROR_CLASS_SERVICES;
|
||||
rpdata->error_code = ERROR_CODE_NO_SPACE_FOR_OBJECT;
|
||||
apdu_len = -1;
|
||||
apdu_len = BACNET_STATUS_ERROR;
|
||||
break;
|
||||
}
|
||||
}
|
||||
@@ -434,14 +434,14 @@ int Multistate_Input_Read_Property(
|
||||
} else {
|
||||
rpdata->error_class = ERROR_CLASS_PROPERTY;
|
||||
rpdata->error_code = ERROR_CODE_INVALID_ARRAY_INDEX;
|
||||
apdu_len = -1;
|
||||
apdu_len = BACNET_STATUS_ERROR;
|
||||
}
|
||||
}
|
||||
break;
|
||||
default:
|
||||
rpdata->error_class = ERROR_CLASS_PROPERTY;
|
||||
rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
|
||||
apdu_len = -1;
|
||||
apdu_len = BACNET_STATUS_ERROR;
|
||||
break;
|
||||
}
|
||||
/* only array properties can have array options */
|
||||
@@ -449,7 +449,7 @@ int Multistate_Input_Read_Property(
|
||||
(rpdata->array_index != BACNET_ARRAY_ALL)) {
|
||||
rpdata->error_class = ERROR_CLASS_PROPERTY;
|
||||
rpdata->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
|
||||
apdu_len = -1;
|
||||
apdu_len = BACNET_STATUS_ERROR;
|
||||
}
|
||||
|
||||
return apdu_len;
|
||||
|
||||
Reference in New Issue
Block a user