Changed Tturnaround time in MS/TP modules to be a minimum of 2ms, or use a dummy transmit of 4 bytes while the transceiver is disabled. 1ms delay will always give smaller than 1ms of delay due to silence timer tick.
This commit is contained in:
@@ -167,7 +167,7 @@ void RS485_Turnaround_Delay(
|
||||
/* delay after reception before trasmitting - per MS/TP spec */
|
||||
/* wait a minimum 40 bit times since reception */
|
||||
/* at least 1 ms for errors: rounding, clock tick */
|
||||
turnaround_time = 1 + ((Tturnaround * 1000UL) / RS485_Baud);
|
||||
turnaround_time = 2 + ((Tturnaround * 1000UL) / RS485_Baud);
|
||||
while (Timer_Silence() < turnaround_time) {
|
||||
/* do nothing - wait for timer to increment */
|
||||
};
|
||||
@@ -241,7 +241,7 @@ bool RS485_ReceiveError(
|
||||
}
|
||||
|
||||
/****************************************************************************
|
||||
* DESCRIPTION: Return true if data is available
|
||||
* DESCRIPTION: Return true if data is available
|
||||
* RETURN: true if data is available, with the data in the parameter set
|
||||
* ALGORITHM: none
|
||||
* NOTES: none
|
||||
|
||||
Reference in New Issue