Changed ATmega168 port to ATmega328 on Uno R3 with DFR0259 RS485 shield (#784)
* Changed ATmega168 example for ATmega328 on Arduino Uno R3 with DFR0259 RS485 shield. Added ADC interface from BDK port and mapped to some AV objects. Removed MS/TP MAC address DIP switch GPIO and moved MS/TP configuration to AV objects. Added AV units property. Added some Uno R3 Digital Inputs and outputs mapped to some BV. Added AVR EEPROM from BDK port and mapped some non-volatile data including MAC address and max manager and baud rate, device ID and names and description and location.
This commit is contained in:
@@ -0,0 +1,57 @@
|
||||
# Introduction
|
||||
|
||||
This is an Arduino RS485 shield, especially designed for the Arduino
|
||||
controller board. It can easily convert the UART to the RS485.
|
||||
This shield integrates:
|
||||
|
||||
* a standard RS485 port
|
||||
* a mini RS485 port (PH2.0 interface)
|
||||
* RS485 headers
|
||||
* provides the prototyping areas
|
||||
* configurable automatic or manual transmission (RTS) mode
|
||||
* configurable operation or programming mode
|
||||
|
||||
# Specification
|
||||
|
||||
* Power module: +5.0V
|
||||
* Module size: 55mmx53mm
|
||||
* 16 digital IO port (including a I2C interface)
|
||||
* 6 analog IO port and power
|
||||
* Operation/programming mode switch
|
||||
* Automatic/manual transceiver mode switch (When in manual transceiver mode, the enable end is the 2nd digital IO port)
|
||||
* Transceiver indicating LED
|
||||
* Standard RS485 interface, mini RS485 interface(PH2.0) and RS485 pins
|
||||
* prototyping area
|
||||
* Reset button
|
||||
|
||||
# Pin Definition
|
||||
|
||||

|
||||
|
||||
## Operation and programming mode switch:
|
||||
|
||||
* To OFF, you can download the program for the Arduino controller.
|
||||
* To ON, the shield will convert the UART to the RS485.
|
||||
|
||||
## Transceiver mode switch:
|
||||
|
||||
* To AUTO, the shield is automatically sending and receiving data so you
|
||||
do not care about operation timing
|
||||
* To MANU, the shield is in manual transceiver status, and the enable end
|
||||
is the 2nd digital IO port. Enabling high-side power Ping to sending
|
||||
state while the low level of the receiving state.
|
||||
|
||||
# Usage Setup
|
||||
|
||||
When the RS485 shield is installed on your Arduino controller,
|
||||
and then you will wire the RS485 shiled with USB-RS485 converter
|
||||
to connect terminals, namely: A pair of A, B on B, GND on GND,
|
||||
then download the following sample code.
|
||||
|
||||
Note: Downloading code, run / program mode switch must hit the OFF position,
|
||||
otherwise it will lead to the download fails. When downloaded, it is complete
|
||||
to ON, and the shield to normal use).
|
||||
|
||||
# Schematic
|
||||
|
||||

|
||||