@@ -56,24 +56,28 @@ static binary_output_write_present_value_callback
|
||||
Binary_Output_Write_Present_Value_Callback;
|
||||
|
||||
/* These three arrays are used by the ReadPropertyMultiple handler */
|
||||
static const int Properties_Required[] = { PROP_OBJECT_IDENTIFIER,
|
||||
PROP_OBJECT_NAME,
|
||||
PROP_OBJECT_TYPE,
|
||||
PROP_PRESENT_VALUE,
|
||||
PROP_STATUS_FLAGS,
|
||||
PROP_EVENT_STATE,
|
||||
PROP_OUT_OF_SERVICE,
|
||||
PROP_POLARITY,
|
||||
PROP_PRIORITY_ARRAY,
|
||||
PROP_RELINQUISH_DEFAULT,
|
||||
static const int Properties_Required[] = {
|
||||
/* unordered list of required properties */
|
||||
PROP_OBJECT_IDENTIFIER,
|
||||
PROP_OBJECT_NAME,
|
||||
PROP_OBJECT_TYPE,
|
||||
PROP_PRESENT_VALUE,
|
||||
PROP_STATUS_FLAGS,
|
||||
PROP_EVENT_STATE,
|
||||
PROP_OUT_OF_SERVICE,
|
||||
PROP_POLARITY,
|
||||
PROP_PRIORITY_ARRAY,
|
||||
PROP_RELINQUISH_DEFAULT,
|
||||
#if (BACNET_PROTOCOL_REVISION >= 17)
|
||||
PROP_CURRENT_COMMAND_PRIORITY,
|
||||
PROP_CURRENT_COMMAND_PRIORITY,
|
||||
#endif
|
||||
-1 };
|
||||
-1
|
||||
};
|
||||
|
||||
static const int Properties_Optional[] = { PROP_RELIABILITY, PROP_DESCRIPTION,
|
||||
PROP_ACTIVE_TEXT, PROP_INACTIVE_TEXT,
|
||||
-1 };
|
||||
static const int Properties_Optional[] = {
|
||||
/* unordered list of optional properties */
|
||||
PROP_RELIABILITY, PROP_DESCRIPTION, PROP_ACTIVE_TEXT, PROP_INACTIVE_TEXT, -1
|
||||
};
|
||||
|
||||
static const int Properties_Proprietary[] = { -1 };
|
||||
|
||||
@@ -987,6 +991,13 @@ int Binary_Output_Read_Property(BACNET_READ_PROPERTY_DATA *rpdata)
|
||||
(rpdata->application_data_len == 0)) {
|
||||
return 0;
|
||||
}
|
||||
if (!property_lists_member(
|
||||
Properties_Required, Properties_Optional, Properties_Proprietary,
|
||||
rpdata->object_property)) {
|
||||
rpdata->error_class = ERROR_CLASS_PROPERTY;
|
||||
rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
|
||||
return BACNET_STATUS_ERROR;
|
||||
}
|
||||
apdu = rpdata->application_data;
|
||||
apdu_size = rpdata->application_data_len;
|
||||
switch (rpdata->object_property) {
|
||||
@@ -1073,7 +1084,6 @@ int Binary_Output_Read_Property(BACNET_READ_PROPERTY_DATA *rpdata)
|
||||
apdu_len =
|
||||
encode_application_character_string(&apdu[0], &char_string);
|
||||
break;
|
||||
#if (BACNET_PROTOCOL_REVISION >= 17)
|
||||
case PROP_CURRENT_COMMAND_PRIORITY:
|
||||
i = Binary_Output_Present_Value_Priority(rpdata->object_instance);
|
||||
if ((i >= BACNET_MIN_PRIORITY) && (i <= BACNET_MAX_PRIORITY)) {
|
||||
@@ -1082,7 +1092,6 @@ int Binary_Output_Read_Property(BACNET_READ_PROPERTY_DATA *rpdata)
|
||||
apdu_len = encode_application_null(&apdu[0]);
|
||||
}
|
||||
break;
|
||||
#endif
|
||||
default:
|
||||
rpdata->error_class = ERROR_CLASS_PROPERTY;
|
||||
rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
|
||||
|
||||