Added test for shed type percent.
This commit is contained in:
@@ -404,8 +404,10 @@ static void testLoadControlStateMachine(void)
|
||||
BACNET_DATE_TIME bdatetime = { 0 };
|
||||
uint32_t object_instance = 1234;
|
||||
BACNET_OBJECT_PROPERTY_REFERENCE object_property_reference;
|
||||
bool status;
|
||||
uint32_t update_interval;
|
||||
bool status = false;
|
||||
BACNET_SHED_LEVEL shed_level = { 0 };
|
||||
BACNET_SHED_STATE shed_state = BACNET_SHED_INACTIVE;
|
||||
uint32_t update_interval = 0;
|
||||
|
||||
test_setup(object_instance);
|
||||
status = Load_Control_Valid_Instance(object_instance);
|
||||
@@ -666,6 +668,65 @@ static void testLoadControlStateMachine(void)
|
||||
priority = Test_Present_Value_Priority();
|
||||
zassert_equal(16, priority, NULL);
|
||||
test_teardown(object_instance);
|
||||
/* SHED TYPE PERCENT - default value 100% */
|
||||
test_setup(object_instance);
|
||||
status = Load_Control_Valid_Instance(object_instance);
|
||||
zassert_true(status, NULL);
|
||||
status = Load_Control_Update_Interval_Set(object_instance, 0);
|
||||
zassert_true(status, NULL);
|
||||
Load_Control_WriteProperty_Enable(object_instance, true);
|
||||
shed_level.type = BACNET_SHED_TYPE_PERCENT;
|
||||
shed_level.value.percent = 100;
|
||||
status =
|
||||
Load_Control_Requested_Shed_Level_Set(object_instance, &shed_level);
|
||||
zassert_true(status, NULL);
|
||||
Load_Control_WriteProperty_Start_Time(
|
||||
object_instance, 2007, 2, 27, 15, 0, 0, 0);
|
||||
Load_Control_WriteProperty_Shed_Duration(object_instance, 5);
|
||||
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 0, 0);
|
||||
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
|
||||
Load_Control_Timer(object_instance, 1);
|
||||
shed_state = Load_Control_Present_Value(object_instance);
|
||||
zassert_equal(shed_state, BACNET_SHED_REQUEST_PENDING, NULL);
|
||||
Load_Control_Timer(object_instance, 1);
|
||||
shed_state = Load_Control_Present_Value(object_instance);
|
||||
zassert_equal(shed_state, BACNET_SHED_INACTIVE, NULL);
|
||||
test_teardown(object_instance);
|
||||
/* SHED TYPE PERCENT - 20% */
|
||||
test_setup(object_instance);
|
||||
status = Load_Control_Valid_Instance(object_instance);
|
||||
zassert_true(status, NULL);
|
||||
status = Load_Control_Update_Interval_Set(object_instance, 0);
|
||||
zassert_true(status, NULL);
|
||||
Load_Control_WriteProperty_Enable(object_instance, true);
|
||||
shed_level.type = BACNET_SHED_TYPE_PERCENT;
|
||||
shed_level.value.percent = 20;
|
||||
status =
|
||||
Load_Control_Requested_Shed_Level_Set(object_instance, &shed_level);
|
||||
zassert_true(status, NULL);
|
||||
Load_Control_WriteProperty_Start_Time(
|
||||
object_instance, 2007, 2, 27, 15, 0, 0, 0);
|
||||
Load_Control_WriteProperty_Shed_Duration(object_instance, 5);
|
||||
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 0, 0);
|
||||
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
|
||||
Load_Control_Timer(object_instance, 1);
|
||||
shed_state = Load_Control_Present_Value(object_instance);
|
||||
zassert_equal(shed_state, BACNET_SHED_REQUEST_PENDING, NULL);
|
||||
/* configure for non-compliance */
|
||||
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 2, 0);
|
||||
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
|
||||
Load_Control_Timer(object_instance, 1);
|
||||
shed_state = Load_Control_Present_Value(object_instance);
|
||||
zassert_equal(shed_state, BACNET_SHED_NON_COMPLIANT, NULL);
|
||||
/* configure for compliance */
|
||||
priority = Load_Control_Priority_For_Writing(object_instance);
|
||||
Test_Present_Value_Priority_Set(20.0f, priority);
|
||||
datetime_set_values(&bdatetime, 2007, 2, 27, 15, 0, 3, 0);
|
||||
datetime_timesync(&bdatetime.date, &bdatetime.time, false);
|
||||
Load_Control_Timer(object_instance, 1);
|
||||
shed_state = Load_Control_Present_Value(object_instance);
|
||||
zassert_equal(shed_state, BACNET_SHED_COMPLIANT, NULL);
|
||||
test_teardown(object_instance);
|
||||
}
|
||||
|
||||
#if defined(CONFIG_ZTEST_NEW_API)
|
||||
|
||||
Reference in New Issue
Block a user