Issues/issue 513 how to reinitialize a bacnet stack on windows (#514)
* Check init flag before cleaning up WSA for BACnet/IP * Check for valid socket before cleaning up WSA for BACnet/IPv6 --------- Co-authored-by: Steve Karg <skarg@users.sourceforge.net>
This commit is contained in:
+6
-5
@@ -375,7 +375,7 @@ int bip6_send_mpdu(BACNET_IP6_ADDRESS *dest, uint8_t *mtu, uint16_t mtu_len)
|
||||
uint16_t addr16[8];
|
||||
|
||||
/* assumes that the driver has already been initialized */
|
||||
if (BIP6_Socket < 0) {
|
||||
if (BIP6_Socket == INVALID_SOCKET) {
|
||||
return 0;
|
||||
}
|
||||
/* load destination IP address */
|
||||
@@ -443,7 +443,7 @@ uint16_t bip6_receive(
|
||||
uint16_t i = 0;
|
||||
|
||||
/* Make sure the socket is open */
|
||||
if (BIP6_Socket < 0) {
|
||||
if (BIP6_Socket == INVALID_SOCKET) {
|
||||
return 0;
|
||||
}
|
||||
/* we could just use a non-blocking socket, but that consumes all
|
||||
@@ -503,10 +503,11 @@ uint16_t bip6_receive(
|
||||
*/
|
||||
void bip6_cleanup(void)
|
||||
{
|
||||
if (BIP6_Socket != -1) {
|
||||
closesocket(BIP6_Socket);
|
||||
if (BIP6_Socket == INVALID_SOCKET) {
|
||||
return;
|
||||
}
|
||||
BIP6_Socket = -1;
|
||||
closesocket(BIP6_Socket);
|
||||
BIP6_Socket = INVALID_SOCKET;
|
||||
WSACleanup();
|
||||
|
||||
return;
|
||||
|
||||
Reference in New Issue