Fixed out-of-service writability to be consistent with present-value in objects using Write_Enabled flag (#921)

This commit is contained in:
Steve Karg
2025-02-20 09:42:15 -06:00
committed by GitHub
parent 97490dacb1
commit 08f152b4ac
7 changed files with 301 additions and 35 deletions
+59 -8
View File
@@ -282,7 +282,7 @@ BACNET_BINARY_PV Binary_Input_Present_Value(uint32_t object_instance)
/**
* @brief For a given object instance-number, checks the present-value for COV
* @param pObject - specific object with valid data
* @param value - floating point analog value
* @param value - binary value
*/
static void Binary_Input_Present_Value_COV_Detect(
struct object_data *pObject, BACNET_BINARY_PV value)
@@ -294,6 +294,21 @@ static void Binary_Input_Present_Value_COV_Detect(
}
}
/**
* @brief For a given object instance-number, checks the out-of-service for COV
* @param pObject - specific object with valid data
* @param value - out-of-service value
*/
static void
Binary_Input_Out_Of_Service_COV_Detect(struct object_data *pObject, bool value)
{
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
}
}
/**
* @brief For a given object instance-number, returns the out-of-service
* property value
@@ -326,10 +341,8 @@ void Binary_Input_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = Binary_Input_Object(object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Out_Of_Service = value;
pObject->Change_Of_Value = true;
}
Binary_Input_Out_Of_Service_COV_Detect(pObject, value);
pObject->Out_Of_Service = value;
}
return;
@@ -520,7 +533,7 @@ bool Binary_Input_Present_Value_Set(
* For a given object instance-number, sets the present-value
*
* @param object_instance - object-instance number of the object
* @param value - floating point analog value
* @param value - binary present-value
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
@@ -570,6 +583,43 @@ static bool Binary_Input_Present_Value_Write(
return status;
}
/**
* For a given object instance-number, sets the out-of-service flag
*
* @param object_instance - object-instance number of the object
* @param value - boolean out-of-service value
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
* @return true if value is set, or false if not set or error occurred
*/
static bool Binary_Input_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = Binary_Input_Object(object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
Binary_Input_Out_Of_Service_COV_Detect(pObject, value);
pObject->Out_Of_Service = value;
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* @brief Get the object name
* @param object_instance - object-instance number of the object
@@ -1081,8 +1131,9 @@ bool Binary_Input_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
Binary_Input_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = Binary_Input_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
case PROP_POLARITY:
+57 -5
View File
@@ -262,6 +262,21 @@ bool BitString_Value_Out_Of_Service(uint32_t object_instance)
return value;
}
/**
* @brief For a given object instance-number, checks the out-of-service for COV
* @param pObject - specific object with valid data
* @param value - out-of-service value
*/
static void BitString_Value_Out_Of_Service_COV_Detect(
struct object_data *pObject, bool value)
{
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
}
}
/**
* @brief For a given object instance-number, set the out of service value.
* @param object_instance - object-instance number of the object
@@ -273,15 +288,51 @@ void BitString_Value_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = BitString_Value_Object(object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
BitString_Value_Out_Of_Service_COV_Detect(pObject, value);
pObject->Out_Of_Service = value;
}
return;
}
/**
* For a given object instance-number, sets the out of service flag
* from WriteProperty service
*
* @param object_instance - object-instance number of the object
* @param value - new value
* @param error_class - BACnet error class
* @param error_code - BACnet error code
*
* @return true if value is set, or false if not set or error occurred
*/
static bool BitString_Value_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = BitString_Value_Object(object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
BitString_Value_Out_Of_Service_COV_Detect(pObject, value);
pObject->Out_Of_Service = value;
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* @brief For a given object instance-number, read the reliability value.
* @param object_instance - object-instance number of the object
@@ -659,8 +710,9 @@ bool BitString_Value_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
BitString_Value_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = BitString_Value_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
default:
-2
View File
@@ -47,7 +47,6 @@ struct object_data {
bool Out_Of_Service : 1;
bool Blink_Warn_Enable : 1;
bool Egress_Active : 1;
bool Changed : 1;
bool Polarity : 1;
};
/* Key List for storing the object data sorted by instance number */
@@ -472,7 +471,6 @@ static void Present_Value_Relinquish_Handler(uint32_t object_instance)
value = Priority_Array_Value(pObject, current_priority);
}
if (pObject->Feedback_Value != value) {
pObject->Changed = true;
if ((!pObject->Out_Of_Service) &&
(Binary_Lighting_Output_Write_Value_Callback)) {
Binary_Lighting_Output_Write_Value_Callback(
+40 -3
View File
@@ -288,9 +288,9 @@ void Binary_Value_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = Binary_Value_Object(object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Out_Of_Service = value;
pObject->Change_Of_Value = true;
}
pObject->Out_Of_Service = value;
}
return;
@@ -525,6 +525,42 @@ static bool Binary_Value_Present_Value_Write(
return status;
}
/**
* For a given object instance-number, sets the out-of-service flag if writable
*
* @param object_instance - object-instance number of the object
* @param value - binary value
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
* @return true if flag is set, false if errors occurred
*/
static bool Binary_Value_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = Binary_Value_Object(object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
Binary_Value_Out_Of_Service_Set(object_instance, value);
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* @brief Get the object name
* @param object_instance - object-instance number of the object
@@ -1004,8 +1040,9 @@ bool Binary_Value_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
Binary_Value_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = Binary_Value_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
#if defined(INTRINSIC_REPORTING) && (BINARY_VALUE_INTRINSIC_REPORTING)
+48 -7
View File
@@ -317,7 +317,7 @@ uint32_t Multistate_Input_Present_Value(uint32_t object_instance)
/**
* @brief For a given object instance-number, checks the present-value for COV
* @param pObject - specific object with valid data
* @param value - floating point analog value
* @param value - multistate value
*/
static void Multistate_Input_Present_Value_COV_Detect(
struct object_data *pObject, uint32_t value)
@@ -359,7 +359,7 @@ bool Multistate_Input_Present_Value_Set(
* For a given object instance-number, sets the present-value
*
* @param object_instance - object-instance number of the object
* @param value - floating point analog value
* @param value - state value 1..N
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
@@ -372,12 +372,14 @@ static bool Multistate_Input_Present_Value_Write(
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
uint32_t old_value = 1;
unsigned max_states;
struct object_data *pObject;
pObject = Multistate_Input_Object(object_instance);
if (pObject) {
if (value <= UINT32_MAX) {
max_states = state_name_count(pObject->State_Text);
if ((value >= 1) && (value <= max_states)) {
if (pObject->Write_Enabled) {
old_value = pObject->Present_Value;
Multistate_Input_Present_Value_COV_Detect(pObject, value);
@@ -439,13 +441,51 @@ void Multistate_Input_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = Multistate_Input_Object(object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
pObject->Out_Of_Service = value;
pObject->Change_Of_Value = true;
}
return;
}
/**
* For a given object instance-number, sets the out-of-service state
*
* @param object_instance - object-instance number of the object
* @param value - out-of-service state
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
* @return true if value is set, false if error occurred
*/
static bool Multistate_Input_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = Multistate_Input_Object(object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
Multistate_Input_Out_Of_Service_Set(object_instance, value);
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* @brief For a given object instance-number, loads the object-name into
* a characterstring. Note that the object name must be unique
@@ -831,8 +871,9 @@ bool Multistate_Input_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
Multistate_Input_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = Multistate_Input_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
default:
+47 -6
View File
@@ -317,7 +317,7 @@ uint32_t Multistate_Value_Present_Value(uint32_t object_instance)
/**
* @brief For a given object instance-number, checks the present-value for COV
* @param pObject - specific object with valid data
* @param value - floating point analog value
* @param value - multistate value
*/
static void Multistate_Value_Present_Value_COV_Detect(
struct object_data *pObject, uint32_t value)
@@ -359,7 +359,7 @@ bool Multistate_Value_Present_Value_Set(
* For a given object instance-number, sets the present-value
*
* @param object_instance - object-instance number of the object
* @param value - floating point analog value
* @param value - multistate value
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
@@ -374,10 +374,12 @@ static bool Multistate_Value_Present_Value_Write(
bool status = false;
struct object_data *pObject;
uint32_t old_value = 1;
unsigned max_states = 0;
pObject = Multistate_Value_Object(object_instance);
if (pObject) {
if (value <= UINT32_MAX) {
max_states = state_name_count(pObject->State_Text);
if ((value >= 1) && (value <= max_states)) {
if (pObject->Write_Enabled) {
old_value = pObject->Present_Value;
Multistate_Value_Present_Value_COV_Detect(pObject, value);
@@ -439,13 +441,51 @@ void Multistate_Value_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = Multistate_Value_Object(object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
pObject->Out_Of_Service = value;
pObject->Change_Of_Value = true;
}
return;
}
/**
* For a given object instance-number, sets the out-of-service state
*
* @param object_instance - object-instance number of the object
* @param value - out-of-service state
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
* @return true if value is set, false if not or error occurred
*/
static bool Multistate_Value_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = Multistate_Value_Object(object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
Multistate_Value_Out_Of_Service_Set(object_instance, value);
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* @brief For a given object instance-number, loads the object-name into
* a characterstring. Note that the object name must be unique
@@ -833,8 +873,9 @@ bool Multistate_Value_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
Multistate_Value_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = Multistate_Value_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
default:
+50 -4
View File
@@ -171,7 +171,7 @@ bool Time_Value_Present_Value(uint32_t object_instance, BACNET_TIME *value)
/**
* @brief For a given object instance-number, checks the present-value for COV
* @param pObject - specific object with valid data
* @param value - floating point analog value
* @param value - time value
*/
static void Time_Value_Present_Value_COV_Detect(
struct object_data *pObject, const BACNET_TIME *value)
@@ -240,7 +240,13 @@ static bool Time_Value_Present_Value_Write(
datetime_copy_time(&old_value, &pObject->Present_Value);
Time_Value_Present_Value_COV_Detect(pObject, value);
datetime_copy_time(&pObject->Present_Value, value);
if (Time_Value_Write_Present_Value_Callback) {
if (pObject->Out_Of_Service) {
/* The physical point that the object represents
is not in service. This means that changes to the
Present_Value property are decoupled from the
physical point when the value of Out_Of_Service
is true. */
} else if (Time_Value_Write_Present_Value_Callback) {
Time_Value_Write_Present_Value_Callback(
object_instance, &old_value, value);
}
@@ -292,6 +298,9 @@ bool Time_Value_Out_Of_Service_Set(uint32_t object_instance, bool value)
pObject = Keylist_Data(Object_List, object_instance);
if (pObject) {
if (pObject->Out_Of_Service != value) {
pObject->Change_Of_Value = true;
}
pObject->Out_Of_Service = value;
status = true;
}
@@ -299,6 +308,42 @@ bool Time_Value_Out_Of_Service_Set(uint32_t object_instance, bool value)
return status;
}
/**
* For a given object instance-number, sets the out-of-service flag
*
* @param object_instance - object-instance number of the object
* @param value - indicator of 'Out-of-service'
* @param error_class - the BACnet error class
* @param error_code - BACnet Error code
*
* @return true if value is set, or false if not or error occurred
*/
static bool Time_Value_Out_Of_Service_Write(
uint32_t object_instance,
bool value,
BACNET_ERROR_CLASS *error_class,
BACNET_ERROR_CODE *error_code)
{
bool status = false;
struct object_data *pObject;
pObject = Keylist_Data(Object_List, object_instance);
if (pObject) {
if (pObject->Write_Enabled) {
Time_Value_Out_Of_Service_Set(object_instance, value);
status = true;
} else {
*error_class = ERROR_CLASS_PROPERTY;
*error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
}
} else {
*error_class = ERROR_CLASS_OBJECT;
*error_code = ERROR_CODE_UNKNOWN_OBJECT;
}
return status;
}
/**
* For a given object instance-number, loads the object-name into
* a characterstring. Note that the object name must be unique
@@ -619,8 +664,9 @@ bool Time_Value_Write_Property(BACNET_WRITE_PROPERTY_DATA *wp_data)
status = write_property_type_valid(
wp_data, &value, BACNET_APPLICATION_TAG_BOOLEAN);
if (status) {
Time_Value_Out_Of_Service_Set(
wp_data->object_instance, value.type.Boolean);
status = Time_Value_Out_Of_Service_Write(
wp_data->object_instance, value.type.Boolean,
&wp_data->error_class, &wp_data->error_code);
}
break;
default: